Typical Performance Values

Principle of the Earth Bond
1) Easy Assembly 2) Tensile Stress 3) Contact Areas
Electrical Performance: Aluminium Plate
Part Number 80958M6 80959M10 80960M6 80961M10
Electrical resistance measured at a point between the terminal lug (copper tin plated) and the aluminium plate 60 micro ohms
T = 2 mm
50 micro ohms
T = 2 mm
60 micro ohms
T = 4 mm
20 micro ohms
T = 4 mm
Withstand short circuit test – 3 passes of high intensity current with no degradation of the connection 10 Ka 20 Ka 10 Ka 20 Ka
Corrosion Test: 500 hours 90 micro ohms
T = 2 mm
50 micro ohms
T = 4 mm
- -
T = Plate Thickness
Mechanical Performance: Aluminium Plate
Part Number 80958M6 80959M10 80960M6 80961M10
Tensile force applied to the dowel or threaded stud to remove earth bond from the plate 250 daN
T = 2 mm
200 daN
T = 2 mm
300 daN
T = 4 mm
500 daN
T = 4 mm
Bending moment (IEC60068-2-21). Force applied at a point 5 mm from the end of the thread 34 daN
T = 1.5 mm
100 daN
T = 2 mm
200 daN
T = 4 mm
300 daN
T = 4 mm
Pressure Seal: Pressure applied to both sides of bond for 2 hours with no leak between bush and plate 6 Bar 6 Bar 6 Bar 6 Bar
T = Plate Thickness
Mechanical Performance: Steel + Stainless Steel Plate
Part Number 80958M6 80959M10 80960M6 80961M10
Electrical resistance measured at a point between the terminal lug (copper tin plated) and the steel plate 25 micro ohms
T = 2 mm
20 micro ohms
T = 2 mm
25 micro ohms
T = 4 mm
20 micro ohms
T = 4 mm
Electrical resistance measured at a point between the terminal lug (copper tin plated) and the stainless steel plate 120 micro ohms
T = 2 mm
70 micro ohms
T = 2 mm
75 micro ohms
T = 4 mm
60 micro ohms
T = 4 mm
With stand short circuit test-3 passes of high intensity current with no degradation of the connection. 10 Ka 15 Ka 10 Ka 20 Ka
Corrosion test: 500 hours: 2 mm steel plate 30 micro ohms 25 micro ohms - -
On 2 mm stainless steel plate 150 micro ohms 90 micro ohms - -
T = Plate Thickness
Mechanical Performance: Steel + Stainless Steel Plate
Part Number 80958M6 80959M10 80960M6 80961M10
Tensile force applied to the dowel or threaded stud to remove earth bond from the plate 400 daN
T = 2 mm
500 daN
T = 2 mm
500 daN
T = 4 mm
800 daN
T = 4 mm
Bending moment (IEC60068-2-21). Force applied at a point 5 mm from the end of the thread 100 daN
T = 1.5 mm
190 daN
T = 2 mm
200 daN
T = 4 mm
330 daN
T = 4 mm
Pressure seal: Pressure applied to both sides of bond for 2 hours with no leak between bond and plate 6 Bar 6 Bar 6 Bar 6 Bar
T = Plate Thickness



About Us       Documentation       Site Map       Use of Cookies       Website Terms and Conditions
Glenair UK Ltd 40 Lower Oakham Way Oakham Business Park Mansfield, Notts NG18 5BY Tel: +44 1623 638100 Fax: +44 1623 638111 email: sales@glenair.co.uk  or Webmaster
VAT Registration No 118 4718 64
Copyright © 2009-2012 Glenair UK Ltd. All Rights Reserved
Glenair France    Glenair GmbH    Glenair Ibérica    Glenair Inc    Glenair Italy    Glenair Nordic